Construction
Component | Specification |
---|---|
Conductor | Aluminium class 2 according to EN 60228 and IEC 60228. |
Insulation | Cross-linked polyethylene type XLPE according to IEC 60502-1. Natural colour. |
Outer sheath | Polyethylene halogen free and UV resistant, type ST7 according to IEC 60502-1 with extra thickness as protection for direct buried cables. Black colour. |
Characteristics
Electrical performance
Feature | Specification |
---|---|
Low voltage | 1.5/1.5 (1.8) kV DC according to EN 50618. 1.8/3 (3.6) kV AC according to IEC 60502-1. |
Thermal performance
Feature | Specification |
---|---|
Maximum conductor temperature | 90°C |
Maximum short-circuit temperature | 250°C (max. 5 s). |
Minimum service temperature | -40°C (fixed and protected installations). |
Minimum installation and handling temperature | 0°C (on cable surface). |
Fire performance
Feature | Specification |
---|---|
Halogen free | According to EN 60754-1 / IEC 60754-1. |
Low corrosive gases emission | According to EN 60754-2 / IEC 60754-2. |
Mechanical performance
Feature | Specification |
---|---|
Minimum bending radius | 5x cable diameter. |
Impact resistance | AG4 (≤ 40 J) Extra high severity according to NF C 33-226. |
Abrasion | According to NF C 33-226. |
Environmental performance
Feature | Specification |
---|---|
UV Resistant | According to EN 50618. |
Water resistance | AD8 Submersion. |
Installation conditions
Condition | Details |
---|---|
Open Air | Suitable |
Buried | Suitable |