Single-phase DC/AC control panels ISL0202CX06 ISL11MSNA03251

DC Input from Photovoltaic Field

  • Up to 2 DC inputs from the photovoltaic field
  • Up to 2 DC outputs to the inverter
  • DC connections via Cabur Linea 4 connectors
  • Possibility to manage up to 2 MPPTs
  • Class A differential switch
  • Magnetic thermal circuit breaker from 6kA to 10kA
  • AC and DC surge protectors
  • For 600V or 1000V systems
  • Compliant with CEI EN 61439-2 standard

(1) With a single disconnect switch, both DC circuits from the field are interrupted simultaneously.

Description

DC Circuit

Version Code ISL0202CX06 ISL11MSNA03251
DC Circuit
Number of input strings 2 1
Number of MPPT outputs 2 1
Maximum input voltage V 600 1000
Maximum current per input string A 10 20
Maximum current per MPPT output A 10 20
Load switch provided 1 (1) 1
Nominal voltage Un V 600 1000
Protection level Up V 2000 3000
Impulse discharge current 8/20 In kA 20 20
Input connection Cabur Linea 4 connectors Cabur Linea 4 connectors
Output connection Cabur Linea 4 connectors Cabur Linea 4 connectors
AC Circuit
Maximum input voltage V 230 230
Maximum input current A 32 25
Nominal frequency Hz 50 50
Type 1P+N 1P+N
Magnetic circuit breaker A 32 25
Intervention curve C C
Short-circuit current kA 6 10
Class A A
Sensitivity A 0.3 0.3
Nominal voltage Un V 230 230
Protection level Up V 1500 1500
Impulse discharge current 8/20 In kA 20 20
Input connection 10 mm² terminal block 10 mm² terminal block
Output connection 10 mm² terminal block 10 mm² terminal block
General Data
Protection degree IP65 IP65
Dimensions (including connector size) 460x340x143 460x340x143