Description
Construction
Component | Specification |
---|---|
Conductor | Aluminium class 2 according to EN 60228 and IEC 60228. |
Insulation | Cross-linked polyethylene, type XLPE according to IEC 60502-1. The standard identification of insulated conductors according to HD 308 is the following:
|
Outer sheath | Special UV resistant PVC, type ST2 according to IEC 60502-1. Black colour. |
Characteristics
Electrical performance
Feature | Specification |
---|---|
Low voltage | 1.5/1.5 (1.8) kV DC according to EN 50618. 1.8/3 (3.6) kV AC according to IEC 60502-1. |
Thermal performance
Feature | Specification |
---|---|
Maximum conductor temperature | 90°C |
Maximum short-circuit temperature | 250°C (max. 5 s). |
Minimum service temperature | -40°C (fixed and protected installations). |
Minimum installation and handling temperature | 0°C (on cable surface). |
Fire performance
Feature | Specification |
---|---|
Flame non-propagation | According to EN 60332-1 / IEC 60332-1. |
Reaction to fire CPR | Eca according to EN 50575. |
Reduced halogen emission | Chlorine < 15%. |
Mechanical performance
Feature | Specification |
---|---|
Minimum bending radius | 5x cable diameter. |
Impact resistance | AG2 Medium severity. |
Environmental performance
Feature | Specification |
---|---|
Chemical resistance | Good. |
Grease & mineral oils resistance | Good. |
UV Resistant | According to EN 50618 and HD 605/A1. |
Water resistance | AD8 Submersion. |
Installation conditions
Condition | Details |
---|---|
Open Air | Suitable |
Buried | Suitable |
In conduit | Suitable |