Interface Protection system in compliance to CEI 0-21

The instrument in 6 DIN module format is an Interface Protection System (SPI) that complies with CEI 0-21 edition 2019-04, with respect to three-phase(*) low-voltage (LV) systems at
50 Hz, with or without neutral (Vn=400V).
It is placed to protect between generation systems and the

public grid, intervening by separating the two should the latter have problems such that one or more of the protection

thresholds provided are exceeded with respect to the voltage
and/or frequency value.
Its operation on the grid is regulated by Terna’s Annex 70.
The protection acts on the contact opening mechanism of
the Device Of Interface (DDI), while also monitoring its actual

state by means of a feedback signal that it reads on its dedicated input. If, as a result of the protection’s intervention, the

opening command is sent to the DDI but it does not detect
it, a second opening command is sent for a device called the

‘back-up’ device that should ensure the generator’s fi nal di-
sconnection from the public grid.

The protection thus has:

  • 3 concatenated voltage measurement inputs, 400Vn.
  • 4 digital inputs for mechanical or NPN contact, respectively named “Remote, “Local Command,” “External Signal,” or more simply redefi ned as “Window Selection Frequency” and finally “DDI feedback.”
  • 2 relay outputs, referred to as “DDI Command” and “Reverse Command”
  • 1 RS485 serial communication port, with Modbus RTU / ASCII communication protocol.
  • 1 alphanumeric LCD display with 2 lines of 16 characters each, backlit.
  • 3 keys for managing the display and programming of parameters of operation.
  • 1 Signal LED.

(*) For single-phase operation, refer to the user’s manual.

Description

Technical Features

Feature Value
Auxiliary Power Supply 90 … 250 Vac or Vdc
Max. absorption 2 VA
Max. applicable phase voltage 500V phase-to-phase
Rated phase voltage measurement 400V phase-to-phase
Direct measuring range 0-500V phase-to-phase TRMS
Input impedance 200 MΩ phase-to-phase
Accuracy 0.5% * Vmax ± 2 digit
Frequency measurement range 19.50 … 100.00 Hz
Operating range 35 – 290V phase-to-neutral
Accuracy 0.01% ± 1 digit
Display Backlit LCD, 16 characters x 2 lines, temp.-20°/+70°C
LED High brightness red, 3mm diameter
Relay Control Outputs 1 NO contact
Contact features 250 Vac / 6Aac (resistive load) / 185W max
Coil-contact insulation 4kVac
Command Inputs 2
Input type NPN / Mechanical Contact
Input voltage 12Vdc
Input current 5 mSec fixed 8.7mA
RS485 Serial Port 115.200 bps
Insulation vs. measuring circuits 3kV
Communication protocol MODBUS RTU / JBUS / ASCII
Programmability and remote controls Yes
Access protection for parameter programming 3-digit password

Mechanical Features

Feature Value
Dimensions Standard 6 DIN modules
Mounting type DIN50022 Guide
Degree of protection IP20 complete luminaire / IP30 front panel

Environmental Conditions

Feature Value
Operating temperature -10 .. +55 °C
Storage temperature -20 .. +70 °C
Relative humidity 10 .. 95 %
Atmospheric pressure 70 .. 110 kPa